FMU120 Series Wall Mounting Ultrasonic Flow Meter
Introduction
The FMU series ultrasonic flow meters are advanced devices designed for accurate, non-intrusive fluid flow measurement in a wide range of industrial applications. These meters utilize ultrasonic wave technology to measure fluid flow without altering the flow state, making them ideal for continuous and real-time monitoring.
Working Principle
The FMU series operates by transmitting ultrasonic waves through the fluid medium. The flow rate is determined by measuring the time it takes for the waves to travel between sensors, converting this data into precise flow rate readings. Because the ultrasonic flow meter does not require installation of measurement elements within the fluid, it introduces no resistance or flow disruption, ensuring that the fluid’s state remains unchanged. This feature makes the FMU series particularly suitable for various industrial environments where maintaining the integrity of the flow is critical.
Features
- Non-Intrusive Measurement: Measures fluid flow using ultrasonic waves without altering the flow state or adding resistance.
- Continuous, Real-Time Monitoring: Ideal for industrial settings requiring accurate, continuous flow measurement.
- Various Measurement Methods: Available in external clamp-on, insertion type, and pipe segment type.
- Wide Measuring Range: Suitable for water, seawater, sewage, alcohol, oils, and other homogeneous liquids that conduct ultrasonic waves.
- Versatile Pipe Compatibility: Works with carbon steel, stainless steel, cast iron, copper, PVC, aluminum, fiberglass-reinforced plastic, cement pipes, and lined pipes.
Applications
The FMU series ultrasonic flow meters are widely used in industries such as water treatment, chemical processing, oil and gas, and HVAC systems. Their non-invasive measurement methods make them ideal for environments where system integrity and continuous flow monitoring are essential.
|
Diameter(mm) |
DN15-DN6000 |
|
Flow speed |
0.3m/s~10m/s |
|
Power supply |
8-36VDC, 85-264VAC |
|
Signal Output |
1 standard isolation RS485 output 1 channel isolated 4-20mA or 0-20mA active output 1 OCT output (programmable pulse width 6-1000ms, factory default 200ms). 1 isolation relay output, Available on output positive, negative, net cumulative pulse and various alarm signals |
|
Signal input |
Two three-wire PT100 platinum resistance input loop, Available to achieve heat measurement function (enthalpy difference method). 3 channels of 4-20mA input optional, accuracy 0.1%, which can input pressure, liquid level, temperature and other signals, can also be used as a digital interface |
|
Display |
2x10 backlight Chinese characters or 2x20 character LCD display (Chinese and English bilingual options) |
|
Operation |
4x4 touch keyboard window operation |
|
Other functions |
Automatically stores data for the previous 512 days, 128 months, and 10 years. It can also record the positive and negative net accumulated flow rates for the last 30 instances. Power-on and power-off times, along with flow rates, can be logged automatically or manually, and all data can be accessed via the Modbus protocol. |
|
Installation mode |
Clamp on/Insertion/Inline |
|
Temperature |
-30 ~ 90℃ |
|
Communication protocol |
MODBUS |
|
Serial port |
RS485 |
|
Protection |
IP65 |
-
Data sheet
Download
FMU DATA SHEET.pdf
-
Manual
-
Certificates

Pressure Measurement
Melt Pressure Measurement
Temperature Measurement
Position measurement
Level measurement
Level Sensor & Transmitter